Cellguard Wireless Monitoring System
Cellguard Wireless Battery Monitoring System |

Free Trial Period
Experience the freedom of Wireless Battery Monitoring at your facility without obligation.
|
|
 | Features | | - Continuous 24/7 online monitoring for system integrity assurance - Full conductance, battery temperature & voltage monitoring for battery state of health analysis - Wireless Communication Architecture ensures proper installation, easy operation, & low maintenance costs - Intercell connection integrity monitoring ensures system effectiveness - Economical total cost of ownership reduces installation cost, hardware price, and system maintenance - Applies test signal to an individual cell or monoblock for high resolution of system state of health - Web enabled communications for remote surveillance - Full monitoring of string charge and discharge current, and discharge performance recording - Advanced notification of battery problems via email or text message - Conductance Advantages: safe, simple, accurate battery prognostics - Industry choice conductance testing is the accepted standard for battery testing |
|
 | Specifications | | Communications Interfaces Ethernet 10 Mbps RS232 or serial USB ( @ 57.6 kbps) 802.15.4 compliant RF transport @ 2.4 GHz Radio Band
Temperature Operating Temperature ( 0 C to +65 C) Storage Temperature ( -10 C to +80 C)
Protection Sensor (2 V & 12 V) Test load and power paths are fused, PolySwitch protection for high heat detection
Power Requirements Base Coordinator Unit Power Powered by 9 V DC wall plug adaptor or powered from VTC (optional) VTC Unit Power Powered from the battery (< 60 mA) 2 V Sensor Power Powered from the battery under surveillance 12 V Sensor Power Powered from the battery under surveillance. Conductance Measurement Range 2V Sensor 100 to 15,000 Siemens 12V Sensor 100 to 4000 Siemens
Strap Resistance Measurement 2 micro Ohms minimum
Test Current 2V & 12V Sensors Test current is approximately 5 Amps RMS
Voltage Measuring Characteristics 2V Sensor Voltage range: 1.75 V to 2.5 V Resolution: +/- 10 mV 12V Sensor Voltage range: 8.7 V to 15.7 V Resolution: +/- 20 milli Volts
Sensor Negative Battery Post Temperature Reading Temperature Range ( 0 C to +65 C) Measurement Accuracy (+/- 2 C)
String Voltage Measurement Input Range 42 to 600 Volts DC
String Current Measurement Float State 300 milli-Amps to 10 Amps Charge State 10 to 200 Amps Discharge State 10 to 200 Amps
Physical Dimensions Base Coordinator Unit 5.08 in x 5.25 in x 2.25 in 12.9 cm x 13.3 cm x 5.7 cm
VTC String Monitor 5.08 in x 5.25 in x 2.25 in 12.9 cm x 13.3 cm x 5.7 cm
2 V & 12 V Sensor 4.45 in x 3.15 in x 1.5 in 11.3 cm x 8 cm x 3.8 cm |
|
|
|